Display Name, Function, Setting Range Factory Default Value
A4 HOLD function OFF
IN
OUT
• Selects OFF or ON for A4 HOLD function.
If alarm HOLD is selected, once A4 activates, A4 output ON status
will be maintained until power is turned OFF.
Not available if (No alarm action) is selected in [A4 type].
• Selection item:
: OFF
: ON
A5 HOLD function OFF
IN
OUT
• Selects OFF or ON for A5 HOLD function.
If alarm HOLD is selected, once A5 activates, A5 output ON status
will be maintained until power is turned OFF.
Not available if (No alarm action) is selected in [A5 type].
• Selection item:
: OFF
: ON
A6 HOLD function OFF
IN
OUT
• Selects OFF or ON for A6 HOLD function.
If alarm HOLD is selected, once A6 activates, A6 output ON status
will be maintained until power is turned OFF.
Not available if (No alarm action) is selected in [A6 type].
• Selection item:
: OFF
: ON
A1 hysteresis 1.0 (SE2EA, SE2RA, SE1EA, SE1RA)
1.0% (SE2AA, SE2VA, SE1AA, SE1VA)
IN
OUT
• Sets A1 action hysteresis
Not available if (No alarm action) is selected in [A1 type].
• Setting range:
SE2EA, SE2RA, SE1EA and SE1RA: 0.1 to 100.0 ( )
SE2AA, SE2VA, SE1AA and SE1VA: 0.1 to 100.0% of input span
A2 hysteresis 1.0 (SE2EA, SE2RA, SE1EA, SE1RA)
1.0% (SE2AA, SE2VA, SE1AA, SE1VA)
IN
OUT
• Sets A2 action hysteresis
Not available if (No alarm action) is selected in [A2 type].
• Setting range:
SE2EA, SE2RA, SE1EA and SE1RA: 0.1 to 100.0 ( )
SE2AA, SE2VA, SE1AA and SE1VA: 0.1 to 100.0% of input span