- 53 -
Performance
Reference input
accuracy (at 23 )
SE2EA and SE1EA:
Within 0.1% of each input span
R, S inputs -50 to 200 (-58 to 392 ): Within 6 (12 )
B input, 0 to 300 (32 to 572 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, Less than 0 (32 ): Within 0.4% of
input span
SE2RA and SE1RA: Within 0.1% of each input span
SE2AA, SE2VA, SE1AA and SE1VA: Within 0.1%
Cold junction temper-
ature compensation
accuracy
Within 1 at -5 to 55 (SE2EA, SE1EA)
Indication accuracy Within Reference input accuracy 1 digit
Input sampling period 25 ms, 125 ms, 250 ms (Selectable via the keypad)
Temperature
coefficient
0.015%/ or less
Insulation resistance Input - Output - Power 10 M or more, at 500 V DC
Dielectric strength Input - Output - Power 2.0 kV AC for 1 minute
General Structure
Case Flame-resistant resin, Color: Light gray
Panel Membrane sheet
Setting Setting by the front keypad
Display Input display: 7-segment, Red LED display 4-digit
Character size: 10 x 4.6 mm (H x W)
Set value display: 7-segment, Red LED display 4-digit
Character size: 10 x 4.6 mm (H x W)
Power indicator: Green LED
CH1 indicator: Yellow LED (SE2 A)
CH2 indicator: Yellow LED (SE2 A)
Installation Specifications
Power supply 100 to 240 V AC 50/60 Hz, 24 V AC/DC 50/60 Hz
Allowable voltage
fluctuation
85 to 264 V AC, 20 to 28 V AC/DC
Power consumption Approx. 9 VA
Ambient temperature -5 to 55
Ambient humidity 35 to 85%RH (non-condensing)
Weight Approx. 200g (socket included)
Mounting DIN rail
External dimensions W30 x H88 x D108mm (socket included)
Attached Functions
Auto-light function Automatically measures and controls brightness of the displays
to conserve power.
Power failure
countermeasure
The setting data is backed up in the non-volatile IC memory.
Self-diagnosis The CPU is monitored by a watchdog timer, and if an abnormal
status is found on the CPU, the instrument is switched to
warm-up status, turning all outputs OFF.
Cold junction
temperature
compensation
Available only for the SE2EA and SE1EA.
This detects the temperature at the connecting terminal between
the thermocouple and the instrument, and always maintains it at
the same status as if the reference junction location temperature
was at 0 (32 ).